CJ1W-PA202

CJ1W-PA202


Specifications
Details



• The replacement notification function can prevent an overflow of the system due to the power lifetime. (CJ1W-PA205C only)
 
• Power Supply Unit provides wide variations according to the system scale up to maximum 25 W.
 
• Power Supply Unit provides wide variations according to the power supply (100 to 240 V AC/ 24 V DC) status.
 
• The output contact during operation enables you to check the CPU operation. (CJ1W-PA205R only)
 
• Conforming to the SEMI-F47 Standard. *
 
* AC input type, 200 V min. input
 
Item Specifications
Model CJ1W-PA205R CJ1W-PA205C CJ1W-PA202
Supply voltage 100 to 240 V AC (wide-range), 50/60 Hz
Operating voltage and
frequency ranges
85 to 264 V AC, 47 to 63 Hz
Power consumption 100 VA max. 50 VA max.
Inrush current *1 At 100 to 120 V AC: 15 A/8 ms max. for cold start at room
temperature
At 200 to 240 V AC: 30 A/8 ms max. for cold start at room
temperature
At 100 to 120 V AC:
20 A/8 ms max. for cold start
at room temperature
At 200 to 240 V AC:
40 A/8 ms max. for cold start
at room temperature
Output capacity *7 5.0 A, 5 V DC (including supply to CPU Unit) 2.8 A, 5 V DC
(including supply to CPU Unit)
0.8 A, 24 V DC 0.4 A, 24 V DC
Total: 25 W max. Total: 14 W max.
Output terminal
(service supply)
Not provided.
RUN output *2 Contact configuration:
SPST-NO
Switch capacity:
250 V AC, 2 A (resistive load)
120 V AC, 0.5 A (inductive
load),
24 V DC, 2A (resistive load)
24 V DC, 2 A (inductive load)
Not provided.
Replacement
notification function
Not provided. With Alarm output (open-
collector output)
30 V DC max., 50 mA max.
Not provided.
Insulation resistance 20 MΩ min. (at 500 V DC)
between AC external and
GR terminals *3
20 MΩ min. (at 500 V DC)
between all external
terminals and GR terminal *3,
and between all alarm output
terminals.
20 MΩ 1 min. (at 250 V DC)
between all alarm output
terminals and GR terminal *3.
20 MΩ min. (at 500 V DC)
between AC external and
GR terminals *3
Dielectric strength *4 2,300 V AC 50/60 Hz for 1 min
between AC external and GR
terminals *3
Leakage current: 10 mA max.
2,300 VAC, 50/60 Hz for 1 min
between all external terminals
and GR terminal *3 and
between all alarm output
terminals with a leakage
current of 10 mA max.
1,000 V AC, 50/60 Hz for 1 min
between all alarm output
terminals and GR terminal *3
with a leakage current of 10
mA max.
2,300 V AC 50/60 Hz for 1 min
between AC external and GR
terminals *3
Leakage current: 10 mA max.
1,000 V AC, 50/60 Hz for 1 minute between DC external and GR terminals *3
Leakage current: 10 mA max.
Noise immunity 2 kV on power supply line (conforming to IEC61000-4-4)
Vibration resistance Conforms to IEC60068-2-6
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz
Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each =
100 min)
Shock resistance Conforms to IEC60068-2-27
147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units)
Ambient operating
temperature
0 to 55 °C
Ambient operating
humidity
10% to 90% (with no
condensation)
10% to 90% (with no
condensation) *5
10% to 90% (with no
condensation)
Atmosphere Must be free from corrosive gases.
Ambient storage
temperature
- 20 to 70 °C (excluding
battery)
- 20 to 75 °C *5 - 20 to 75 °C (excluding
battery)
Grounding Less than 100 Ω
Enclosure Mounted in a panel.
Weight 350 g max. 400 g max. 200 g max.
CPU Rack
dimensions
90.7 to 466.7 × 90 × 65 mm (W × H × D) (not including cables)
Note:
W = a + b + 20 × n + 31 × m + 14.7
a: Power Supply Unit: PA205R and PA205C = 80; PA202 = 45; PD025 = 60; PD022=27
b: CPU Unit: CJ1-H or CJ1 = 62; CJ1M-CPU1[] = 31 *8; CJ1M-CPU2[] = 49 *8
The total width is given by the following: W = 156.7 + n × 20 + m × 31,
where n is the number of 32-point I/O Units or I/O Control Units and m is the number of other
Units.
Safety measures Conforms to cULus and EC Directives.

View more about CJ1W-PA202 on main site